Appendix
223
Rack Mounting
Before working on the rack, make sure that the stabilizers are secured to
the rack, extended to the floor, and that the full weight of the rack rests on
the floor. Install front and side stabilizers on a single rack or front
stabilizers for joined multiple racks before working on the rack.
Always load the rack from the bottom up, and load the heaviest item in the
rack first.
Make sure that the rack is level and stable before extending a device from
the rack.
Use caution when pressing the device rail release latches and sliding a
device into or out of a rack; the slide rails can pinch your fingers.
After a device is inserted into the rack, carefully extend the rail into a
locking position, and then slide the device into the rack.
Do not overload the AC supply branch circuit that provides power to the
rack. The total rack load should not exceed 80 percent of the branch circuit
rating.
Make sure that all equipment used on the rack – including power strips and
other electrical connectors – is properly grounded.
Ensure that proper airflow is provided to devices in the rack.
Ensure that the operating ambient temperature of the rack environment
does not exceed the maximum ambient temperature specified for the
equipment by the manufacturer
Do not step or stand on any device when servicing other devices in a rack.
Stacking
The KVM Over the Net unit has been provided with a protective grounding
terminal. Use a grounding wire to connect the unit’s grounding terminal to a
suitable grounded object. Do not omit this step.
In any installation, please also observe the following:
The building installation should provide a means for connection to
protective grounding and the equipment is to be connected to that means;
A service person should check whether or not the socket-outlet from
which the equipment is to be powered provides a connection to the
building protective grounding. If not, the service person should arrange for
the installation of a Protective Grounding Conductor from the separate
protective grounding terminal to the protective grounding wire in the
building.